Duct Airflow and Sensible Heat

Estimate airflow through a rectangular duct and the dry air's sensible heat change using specified average velocity, density and constant-pressure heat capacity.

Input parameters

The calculator is loading. If it remains unavailable, refresh and ensure JavaScript and page resources are available.

Inputs and calculations stay in this browser. Changing the dimension unit converts both width and height. Inputs are retained for this browser session, including when switching languages.

Results

Estimated temperature-related air enthalpy-rate change
—W

Duct area: — m²
Volume flow: — m³/s · — m³/h
Mass flow: — kg/s

Positive means the outlet temperature is higher; negative means it is lower. Volume flow refers to the duct measurement state. The heat-transfer interpretation requires the conditions below.

Equations

A = width × height
V̇ = A × v
ṁ = ρ × V̇
ΔḢT = ṁ × cp × (Tout − Tin)

Use metres, m/s, kg/m³ and J/(kg·K); Celsius differences equal kelvin differences.

Applicability

  • Steady flow, rectangular clear internal dimensions and cross-section averaged velocity.
  • Dry air at constant mass flow, with negligible pressure effects on enthalpy; density must match the velocity measurement section and the specified average constant-pressure heat capacity must represent the temperature range.
  • When shaft work and kinetic and potential energy changes are negligible and no other mass crosses the boundary, the enthalpy-rate change approximates net heat transfer to the air. When finding equipment heating or cooling duty, include significant fan work and external heat losses in a complete energy balance.
  • Humidity, condensation, latent load, leakage and actual velocity profiles are not calculated. Width and height are converted when the dimension unit changes.

Worked example

0.5 m × 0.3 m at 2 m/s gives 0.3 m³/s. With ρ = 1.2 kg/m³, cp = 1006 J/(kg·K) and heating from 20 to 30 °C, the estimated temperature-related enthalpy-rate change is +3621.6 W; under the conditions above it approximates net heat transfer.

Default density and constant-pressure heat capacity are illustrative. Replace them with values appropriate to the measurement and temperature range.

Dry air reference properties →

Engineering estimate only; verify actual conditions and applicable design requirements.