Log Mean Temperature Difference Calculator

LMTD Calculator

Calculate the log mean temperature difference for a simple parallel-flow or counterflow heat exchanger.

Input parameters

The calculator is loading. If it remains unavailable, refresh and ensure JavaScript and page resources are available.

Inputs and calculations stay in this browser.

Result

Log mean temperature difference
— °C

When the terminal differences are equal, the limit is used. Multipass and crossflow correction factors are not included.

Equation

ΔTlm = (ΔT₁ − ΔT₂) / ln(ΔT₁ / ΔT₂)

When the terminal differences are equal, the limit is used. Multipass and crossflow correction factors are not included.

Applicability

  • For Q̇ ≈ UAΔTlm, assume steady single-pass parallel or counterflow, approximately constant heat-capacity rates and U, and negligible external heat loss. Computing the terminal temperature mean does not establish these conditions.
  • Does not calculate multipass correction factors, phase change, or flow distribution.
  • Both terminal differences must be positive; the hot stream must cool and the cold stream must warm.
  • Temperatures alone cannot establish the energy balance; check flow rates and heat capacities.

Worked example

Example: counterflow with hot 150 → 100 °C and cold 20 → 70 °C has two terminal differences of 80 °C, giving 80 °C.

For engineering estimates; check the operating conditions and applicable requirements for design.