Phase Change Latent Heat Rate Calculator

Calculate latent heat rate for isothermal evaporation or condensation using phase-change mass flow and latent heat at the relevant state.

Input parameters

The calculator is loading. If it remains unavailable, refresh and ensure JavaScript and page resources are available.

Inputs and calculations stay in this browser.

Result

Latent heat rate for the phase-changing fluid
—kW

Positive means heat enters the phase-changing fluid; negative means heat leaves it. This is the latent contribution, not the complete equipment duty.

Equation

Q̇latent = +ṁ hfg (evaporation); Q̇latent = −ṁ hfg (condensation)

ṁ is the mass flow undergoing phase change (kg/s); hfg is the positive latent heat at the corresponding saturation state (kJ/kg). Their product is in kW; direction determines the sign.

Applicability

For isothermal evaporation or condensation at the selected state. The flow is the mass actually changing phase, not an unchecked total flow. The input latent heat must apply to that process; subcooling or superheating sensible heat, heat loss, pressure drop and other energy terms are excluded.

Traceable example

At 100 °C and approximately 101.418 kPa saturation pressure, saturated water has latent heat about 2256.4 kJ/kg. Complete evaporation of 0.1 kg/s absorbs +225.64 kW; complete condensation at the same rate releases −225.64 kW from the fluid. Latent heat varies with saturation state.

See the 100 °C row in the saturated water and steam table →

For engineering estimates; verify the full energy balance, operating conditions and applicable requirements for design.